S7-1200 / S7-1500 Configuration with SCADA from Other Manufacturers
Dedicated to the new generation of students. If we want to communicate our S7-1200 / S7-1500 with SCADA / HMI / OPC Server from other manufacturers, we need to enable it. To do this, we go to the properties of our CPU as shown in the image.
In the properties, we go to the Protection options, we need to give Full access and enable the PUT / GET checkbox to allow communications.
With some manufacturers, in order to access the DBs, they must not be optimized.