Press ESC to close · Ctrl+K to open

Factory Talk View SE - DataLogPro Error

Unable to open the DataLogPro because the HMI server is not available.

Factory Talk View SE - DataLogPro Error

Objective

After installing FactoryTalk View SE v16, we are going to configure variables in the DataLogPro configurator, in this case thinking about a later setup with InfluxDB.

When opening the editor, FactoryTalk View Studio shows an error that seems to point to the HMI Server, but the real origin is in the machine's web configuration. The objective of this article is to pinpoint the fault and solve it without unnecessary detours.

DataLogPro opening fault

The error appears when entering Data Log > DataLogPro inside the FactoryTalk View SE project:

Unable to open the DataLogPro because the HMI server is not available.

The message can make us think about a project or HMI Server problem. However, the HMI Server was available; what was failing was the HTTPS layer used by DataLogPro.

Unable to open the DataLogPro because the HMI server is not available message

Cause of the problem

Checking Internet Information Server (IIS) Manager, we can see that the default site has both HTTP and HTTPS enabled. The problem appears because HTTPS is active, but it does not have a valid certificate assigned to the server.

In this scenario, DataLogPro tries to open its service through that web configuration. If the HTTPS binding is not properly completed with its certificate, FactoryTalk View Studio cannot open the editor and returns the HMI Server error.

As a general criterion, we should always work with HTTPS
Avoid keeping HTTP enabled if it is not necessary.
HTTP and HTTPS bindings for the Default Web Site in IIS Manager

Resolution

The solution is to create or import an SSL certificate and assign it to the HTTPS binding of the Default Web Site in IIS.

A self-signed certificate could be used for a quick test, but it is not the most recommended option. In this case, it was created with a Certificate Manager CA, so the server has a certificate issued by a controlled CA.

Once the certificate is available, open the HTTPS binding, select the certificate in SSL certificate and leave port 443 correctly configured.

IIS HTTPS binding with an SSL certificate selected for the server

We can also check it from Server Certificates in IIS. The server certificate should appear there, with its validity date and the associated private key.

Server certificate visible in IIS Server Certificates

Final check

After assigning the certificate to the HTTPS binding, restart and go back to FactoryTalk View Studio, then open DataLogPro again. The editor now loads correctly and allows you to continue with log group and variable configuration.

This resolves the initial block. In the next article, we will cover the step-by-step configuration of InfluxDB inside FactoryTalk View SE.

DataLogPro opened correctly in FactoryTalk View Studio

Quick summary: if DataLogPro says that the HMI Server is not available right after installing FactoryTalk View SE, check the IIS bindings and the HTTPS certificate first. It is a short check and can save a good amount of time.



Was this article useful?

Share on LinkedIn