Video: from nothing to a running GRAFCET
Two and a half minutes, uncut: creating the steps, declaring the signals, writing a receptivity, hooking elements by dragging, adding a standard time delay, closing the cycle and running the simulation.
A full walkthrough of GrafSim, recorded on the real tool.
What GrafSim is
GrafSim is a GRAFCET editor and simulator that runs entirely in the browser. It is built on the model the IEC 60848 standard requires: the transition is an element in its own right, with its preceding and following steps, and the engine applies the five evolution rules exactly as they are written.
That is not an academic detail. It is what makes it possible to represent an AND convergence that genuinely waits for every branch to arrive, to have two simultaneously fireable transitions fire together, and to have a continuous action drop to zero the moment its step deactivates.
The editor, with the double-square initial step and the actions to the right of each step.
Genuinely to standard
Initial step, transition as a first-class element, the five evolution rules and iteration until a stable situation is reached.
Nothing to install
It opens in the browser and works offline once loaded. Your work is saved on your own machine.
English and Spanish
The whole interface, the help, the guided tutorial and even the comments in the generated PLC code.
Free
No sign-up, no account, no usage limits and no paid tier lurking behind it.
Drawing with the mouse
Move the mouse near a step and a connector appears on its bottom edge. Drag it onto another step and the two get linked: the transition in between is created for you, because in GRAFCET two steps are never joined directly. Drop it on empty space and both the transition and the next step are created at once.
With a step selected you also get buttons to continue the sequence, open divergences or close a loop; and right-clicking anywhere opens a menu with everything you can do there.
The tool ships with a 17-step guided tutorial that advances on its own as you do each thing.
Receptivities and time delays
Receptivities use the notation of the standard and are validated as you type. On top of that, the variables you have declared are suggested for you, filtered by what you have typed so far.
a·b,a+b,!aand parentheses↑aand↓afor rising and falling edgesX3for step activityt/X3/5sfor a standard time delay=1for an always-true receptivity
As you type, declared variables are offered grouped by inputs, outputs and steps.
OR and AND divergences
The bars are not drawn by hand: they are derived from the topology of the diagram. If a step has several outgoing links it is an OR divergence and the bar is single; if it is a transition that has several outgoing links, it is an AND divergence and the bar is double. Always consistent with what is actually drawn.
Simultaneous sequences: double bar at both ends. The convergence waits for both branches.
Sequence selection: single bar, with one transition per branch.
Simulating and watching the signals
While simulating, the active step is painted green with its token, and each transition is coloured by state: amber when it is enabled and green when its receptivity is also true. That shows you why the GRAFCET advances, or why it does not.
Inputs are toggled by clicking them, and you can do it right on the diagram: every variable in a receptivity is a live object. Timers show a progress bar and the remaining seconds, and the timing chart at the bottom plots steps, inputs and outputs.
Simulation running: active step, timer counting down on the transition and the timing chart below.
During simulation the variables panel turns into a switch board.
Standard diagnostics
GrafSim validates the diagram as you draw and flags what the standard does not allow: no initial step, transitions without a preceding or following step, undeclared variables, unreachable steps or steps that deadlock the cycle, and OR divergences whose branches are not mutually exclusive —that last one properly checked, by enumerating the combinations of the variables involved.
Diagnostics also lists the detected structures and logs every firing.
PLC code
Every diagram can be turned into Siemens SCL, CODESYS ST or plain pseudocode for documentation. It is not a text dump: it follows the two-phase structure a cyclic-scan PLC needs —fireable transitions are computed first, then steps are deactivated and activated— which is precisely what guarantees rules 4 and 5 of the standard.
// ─── Phase 1: fireable transitions (rule 2) ─── T1 := X1 AND (start AND part); T4 := X4 AND X5 AND (TRUE); // ─── Phase 2a: deactivate preceding steps (rule 3) ─── IF T1 THEN X1 := FALSE; END_IF; // ─── Phase 2b: activate following steps ─── // This comes after ALL deactivations, so a step that is deactivated // and activated at once stays active (rule 5). IF T1 THEN X2 := TRUE; END_IF; // ─── Actions associated with the steps ─── drill := X2 OR X3; // continuous action N
The code can be copied to the clipboard or downloaded.
Other details
- Light and dark themes, using the site palette.
- Save and open as JSON, and export the diagram as vector SVG, ready to print or drop into a document.
- It imports diagrams from the old GrafSim: every connection becomes a transition, and anything without a standard equivalent is reported.
- Undo and redo with Ctrl+Z, plus autosave in the browser.
- Built-in examples: sequence with a loop, sequence selection and simultaneous sequences.
Dark theme, for the long sessions.
Getting started
Open it and try it in a minute
No sign-up, nothing to install. If it is your first time, the guided tutorial builds a whole GRAFCET with you, step by step.