Scenario
Imagine this scenario: a central SCADA with WinCC Classic version 8.1 Update 6 and several WinCC Unified HMIs distributed in the field.
In this case we can also share the field screens in the WinCC 8.1 SCADA for centralization. This way, the plant HMI panels can be integrated into WinCC Classic through the UnifiedPictureWindow object.
HMI WinCC Unified - field screens
In the HMI projects, we enable Collaboration from the Runtime settings.
We check the IP address of the device.
We enable the certificates required for the communication.
We transfer the project to the HMI.
WinCC 8.1
On the WinCC 8.1 computer, we verify that we are on the same network.
Inside a WinCC 8.1 PDL, we select the UnifiedPictureWindow object.
Note: in this example, the WinCC F1 help does not include information for this object.
We instantiate the object by dragging it into the PDL and then open its properties.
The relevant property is SourceSystem, where the URL of the previously configured Unified HMI must be entered.
Note: in this example the URL is used by name because it was previously configured through a DNS server or the hosts file.
Validation
We download the SCADA to see the result. The connection is established correctly and WinCC 8.1 asks for the Unified HMI credentials.
After logging in, we can see the WinCC Unified HMI content inside WinCC 8.1.
Finally, we check the HMI in a browser and WinCC 8.1 running on its machine.
Siemens Documentation