WinCC Unified Collaboration in WinCC 8.1

Using WinCC Unified screens inside WinCC 8.1 with the UnifiedPictureWindow object.

WinCC Unified Collaboration in WinCC 8.1

Scenario

Imagine this scenario: a central SCADA with WinCC Classic version 8.1 Update 6 and several WinCC Unified HMIs distributed in the field.

In this case we can also share the field screens in the WinCC 8.1 SCADA for centralization. This way, the plant HMI panels can be integrated into WinCC Classic through the UnifiedPictureWindow object.

HMI WinCC Unified - field screens

In the HMI projects, we enable Collaboration from the Runtime settings.

Enabling Collaboration in the WinCC Unified HMI project

We check the IP address of the device.

HMI IP address in the WinCC Unified Collaboration settings

We enable the certificates required for the communication.

Certificates in WinCC Unified Certificate Manager

We transfer the project to the HMI.

WinCC Unified Runtime screen transferred to the HMI

WinCC 8.1

On the WinCC 8.1 computer, we verify that we are on the same network.

Network check using hostname and ipconfig commands

Inside a WinCC 8.1 PDL, we select the UnifiedPictureWindow object.

UnifiedPictureWindow object in the WinCC Smart Objects list

Note: in this example, the WinCC F1 help does not include information for this object.

WinCC help with no results for UnifiedPictureWindow

We instantiate the object by dragging it into the PDL and then open its properties.

The relevant property is SourceSystem, where the URL of the previously configured Unified HMI must be entered.

SourceSystem property of the UnifiedPictureWindow object in WinCC 8.1

Note: in this example the URL is used by name because it was previously configured through a DNS server or the hosts file.

Hosts file with the name used to resolve the Unified HMI

Validation

We download the SCADA to see the result. The connection is established correctly and WinCC 8.1 asks for the Unified HMI credentials.

Unified HMI credential prompt from WinCC 8.1

After logging in, we can see the WinCC Unified HMI content inside WinCC 8.1.

WinCC Unified HMI content displayed in WinCC 8.1

Finally, we check the HMI in a browser and WinCC 8.1 running on its machine.

Unified HMI in a browser and WinCC 8.1 running on the SCADA machine