Remote Device Linx Gateway

Remote access to RSLogix Emulate 5000 using RSLinx Gateway.

Remote Device Linx Gateway

Objective

This practice configures the Remote Device Linx Gateway driver. Requirements are RSLinx Gateway and both computers being in the same workgroup.

The goal is to access devices available on another PC acting as a gateway, specifically RSLogix Emulate 5000, to later use it with FactoryTalk View ME.

Environment with RSLinx Gateway
Computers in the same workgroup

Enable RSLinx Classic Gateway

To enable the gateway function, go to Communications > Configure Gateway and select Enable RSLinx Classic Gateway.

In Client Access List, add the IP of the computer from which the Remote Device Linx Gateway driver will be configured.

RSLinx Classic Gateway enabled
Client access list in RSLinx Gateway

Check the Gateway Computer

The next image shows RSLogix Emulate 5000, the computers in the same workgroup and the computer IP address.

RSLogix Emulate 5000 visible on the gateway computer
IP and workgroup computers

Create the Remote Driver

Now go to the computer where the driver will be configured, where FactoryTalk View Machine Edition is installed to simulate a PanelView.

Add a new driver and choose Remote Device Linx Gateway. Assign a name and enter the IP address of the computer where the driver to access is located.

Adding a new driver in RSLinx
Remote Device Linx Gateway driver selection
Gateway computer IP for the remote driver

Verify Remote Access

If everything is correct, the driver is running and remote access to RSLogix Emulate 5000 is available.

After that, only a new topic for that controller needs to be configured, as used in the FactoryTalk View ME practice.

Remote Device Linx Gateway driver running
Remote access to RSLogix Emulate 5000